Overall Heat Transfer Coefficient

Every shell and tube sizing exercise ends in the same place: Q = U × A × LMTD, and then a long argument about what U should be. Get it wrong and the unit is either 30% oversized (you lose the order on price) or undersized (you lose the customer on performance). This page is the working table our engineers start from, with the assumptions that make each number valid.

Two warnings before the table. First, U is a result, not an input — it falls out of the tube-side and shell-side film coefficients, the wall resistance and the fouling allowances. Second, every figure below is a design starting point for clean-to-moderately-fouled service. If your duty is unusual, the number is wrong until it is calculated.

Where the numbers come from

The overall coefficient is a series of resistances stacked end to end:

1/U = 1/htube + Rfouling,tube + t/kwall + 1/hshell + Rfouling,shell

The dominant term decides everything. In a water-to-water exchanger both films are good and the answer lands in the high hundreds. In an air-cooled exchanger the air-side film is so poor that it drags U down by a factor of thirty, which is why fins exist and why you never compare a bare-tube U with a finned one on the same basis.

Design U-values by duty and fluid pair

All values in W/m²·K, referenced to the outside tube surface unless stated. Ranges assume clean service with a fouling allowance already built in.

ServiceHot sideCold sideTypical UWhat drives it
Cooling waterWaterWater800 – 1,500Tube velocity; below 1 m/s the tube film dominates
Chilled water / HVACWaterWater-glycol600 – 1,200Glycol concentration; 40% glycol costs roughly 20% of htube
Steam heaterSteam condensingWater1,500 – 4,000Non-condensables; 5% air in steam can halve the shell film
Steam condenserSteamCooling water900 – 2,000Tube cleanliness, venting
Oil coolerLube / hydraulic oilWater100 – 350Oil viscosity at wall temperature — the single biggest lever
Thermal oilHeat transfer oilProcess fluid80 – 250Viscosity, and whether the flow is turbulent at all
Brine / chemicalsBrineRefrigerant400 – 900Concentration; falling-film designs sit at the top of the band
Refrigerant condenserRefrigerant condensingWater700 – 1,500Condensing film, tube geometry
Flooded evaporatorRefrigerant boilingBrine / water500 – 1,200Boiling coefficient; oil return
Air cooler (bare tube basis)Process fluidAir25 – 60Face velocity and fin density
Finned air cooler (air-side area basis)Process fluidAir25 – 55Fin efficiency above 10 fins per inch
Flue gas economiserFlue gasWater25 – 60Gas velocity; soot. Ash fouling is not linear
Gas-to-gasFlue gasAir10 – 40Both films poor; extended surface on both sides

Brazed and gasketed plate exchangers are a different class entirely: 3,000 – 7,000 W/m²·K for water-to-water, because the corrugation generates turbulence at Reynolds numbers where a shell and tube unit is still laminar. A plate unit for the same duty is roughly a fifth of the footprint. That is also why it fouls faster in dirty service — the narrow gap that makes it efficient is the same gap that plugs.

Fouling allowance: where sizing actually goes wrong

Fouling resistance is a policy decision, not a physical constant, and it is the most common source of disagreement between a buyer’s datasheet and a factory’s quote. If your specification says 0.0002 m²·K/W on the tube side and ours assumes 0.0001, the two units are not the same unit even though both say “shell and tube”.

FluidFouling resistance m²·K/WPractical note
Treated cooling tower water0.0002 – 0.0004Water treatment quality moves this more than any design choice
River or well water0.0004 – 0.0009Seasonal; size for the worst month, not the average
Seawater, below 50°C0.0002 – 0.0005Titanium or Cu-Ni; velocity above 1.2 m/s to limit settlement
Lube oil0.0002 – 0.0004Keep wall temperature below the oil’s degradation point
Steam (clean)0.0001 – 0.0002Realistic only with good condensate treatment
Refrigerant (clean)0.0001Oil management matters more than the number
Process chemicals0.0003 – 0.001Ask the chemical supplier; do not average

Doubling the fouling allowance on a water-to-water duty typically adds 10–20% to the surface area and 8–15% to the price. That is a cheap insurance policy. Under-specifying it to win a price comparison is how units end up short of duty eighteen months later.

Five checks before you commit to a U-value

  1. Is the tube side actually turbulent? Below Reynolds 10,000 the tube film collapses and the table above stops applying. Small units with low flow are the usual victims — check velocity per tube, not total flow.
  2. What is the wall temperature, not the bulk temperature? For oil coolers the viscosity at the wall sets the coefficient. Use the wall temperature to look up viscosity, then iterate once.
  3. Are you comparing like with like on area? Air coolers are quoted on air-side area, plate units on plate area, shell and tube on outside tube surface. A “U” without a reference area is meaningless.
  4. Has the specification fixed the fouling factor and the material? Both change the answer more than the correlation does.
  5. Is the duty close to a phase change? Condensing and boiling coefficients are not constant along the length. A single U for the whole exchanger is an approximation that gets worse as the duty approaches pure condensation.

Do the calculation properly, then talk to us

Our sizing tools run the same physics as this page: heat load from mass flow and temperature rise, counterflow LMTD, the Bowman-Mueller-Nagle correction factor for one shell pass and two tube passes, and area from U. The full sizing calculation walkthrough takes it step by step with a worked example.

If you would rather skip to a drawing, send us the eight numbers: both flow rates, both inlet temperatures, both outlet temperatures, the two fluids and the design pressure. You will have a budgetary offer with a general arrangement drawing within one working day, and the U-value we used will be stated on it so you can check it against this table.

Frequently asked

What is a good overall heat transfer coefficient for a shell and tube heat exchanger? For water-to-water duty, 800–1,500 W/m²·K is normal. Anything above 1,500 usually means high velocity and a thin tube wall; anything below 600 usually means low velocity, heavy fouling allowance, or a viscous fluid.

Why is the U-value for air so much lower? Air has roughly a twentieth of the thermal conductivity of water and a far lower density, so the air-side film coefficient is 25–60 W/m²·K against 3,000–8,000 for water. Fins add area to compensate; they do not raise the film coefficient itself.

Does a higher U-value always mean a better exchanger? No. It means less area for the duty, which usually means higher pressure drop and faster fouling. The right exchanger is the one with the lowest lifecycle cost, not the smallest surface.

Can you size a unit from a U-value I supply? Yes, but we will recalculate it and tell you if we disagree, in writing, before quoting. See shell and tube heat exchangers for the construction options and TEMA shell types for how the shell arrangement changes the answer.

Save to list