How a Screw Chiller Works

A screw chiller has no pistons, no valves in the gas path and, in most industrial builds, one moving assembly. The compression happens between two intermeshing rotors that trap a pocket of gas and squeeze it continuously along the rotor length. Understanding that single motion explains the capacity control, the oil system, the part-load efficiency curve and most of the failures.

The four states of the refrigerant

Every vapour-compression chiller does the same four things, whatever the compressor:

  1. Evaporation — low-pressure liquid refrigerant boils in the evaporator, taking heat out of the chilled water or glycol circuit.
  2. Compression — the vapour is squeezed from evaporating pressure to condensing pressure. In a screw machine this happens between the rotors.
  3. Condensation — the hot high-pressure gas gives up heat to the condenser water or to air, and becomes liquid.
  4. Expansion — the liquid passes through the expansion device and drops back to evaporating pressure.

The screw compressor only owns step 2. Everything else is heat exchanger and control work, which is why the same compressor in a badly specified package performs badly.

Inside the twin screw compressor

Two helical rotors — a male with convex lobes and a female with matching flutes — rotate inside a close-tolerance housing. As they turn, the space between the lobes opens at the suction port, fills with vapour, closes, and then travels axially while the volume shrinks. Discharge happens when the pocket lines up with the discharge port.

Three consequences follow directly:

Compression is continuous, not pulsed. Gas is being compressed along the whole rotor length at every instant, so the discharge pressure is steady and the machine does not need a receiver to smooth pulses. This is why screw chillers drive large chilled-water systems without the vibration signature of a reciprocating machine.

The built-in volume ratio is fixed by geometry. The ratio of pocket volume at suction to discharge is set by the rotor and port design. If the system’s pressure ratio does not match that built-in ratio, the machine either under-compresses (gas expands back at the port, losing efficiency) or over-compresses (extra work with no benefit). A screw chiller selected for a mild climate and then run in a cold season sits off its design point — which is one reason VSD machines earn their premium in variable-weather duty.

Oil is part of the compression chamber. The rotors need an oil film to seal the clearance between them and to remove heat of compression, and that oil travels with the discharge gas. The oil separator, oil cooler, oil filter and oil return are not accessories; they are part of the compression circuit. A screw chiller with a fouled oil cooler will trip on high discharge temperature long before it trips on anything else.

Capacity control: the slide valve

The classic control is a slide valve that moves axially under the rotors, opening a bypass port back to suction. Sliding it towards the suction end shortens the effective compression length and reduces capacity — typically to about 25–35% of full load before the machine becomes unstable or the oil return suffers.

Below that, the compressor either cycles or a variable-speed drive takes over. VSD screw chillers vary rotor speed instead of bypassing gas, which keeps the built-in volume ratio matched to the actual load and is why they hold a much better part-load curve. The trade is cost, drive losses and a different set of maintenance skills.

Control methodTypical turndownPart-load efficiencyWhere it fits
Slide valve, fixed speed25–100%Falls away below 50% loadSteady process duty, base-loaded plant
Slide valve + VSD10–100%Holds well to 30–40%Variable cooling demand, low ambient seasons
Multiple compressors on one circuitStaging in stepsBest if stages are equal and sequencedRedundancy also required

The economiser, and why it is worth the pipework

Most industrial screw chillers add an economiser: a small heat exchanger that subcools the liquid line and injects the flashed vapour into a port part-way along the rotors. Because that vapour enters at intermediate pressure, the compressor does less work per kilogram of refrigerant reaching the condenser. The gain is typically 5–12% in COP depending on the pressure ratio, which on a machine running 6,000 hours a year is the difference between one and two payback years.

It costs one extra nozzle on the compressor, one small exchanger and some pipework. If a quote does not mention an economiser on a machine above a few hundred kilowatts, ask why.

Water-cooled, air-cooled, evaporative

The compressor is identical; the condenser decides the application.

Water-cooled — a shell and tube condenser with cooling tower water. Smallest footprint, best efficiency, but it needs a tower, pumps and water treatment. See water cooled chillers for the scroll equivalent at smaller capacities.

Air-cooled — a finned coil and fans. No water at all, so it can go on a roof with no plant room, at the cost of a condensing temperature that follows ambient. On a 40°C day an air-cooled machine works much harder than a water-cooled one. Compare air cooled screw chillers and the trade-offs in dry cooler vs cooling tower.

Evaporative — combines a coil with an evaporative spray, getting close to wet-bulb temperature with far less water than a tower. The middle path, and the one most industrial sites choose when water is metered but not forbidden.

What actually fails

In service, the compressor is rarely the problem. The failures we see are:

  • Oil management — low oil pressure, a blocked filter, a failed oil cooler. Discharge temperature alarms are usually the first symptom.
  • Condenser fouling — scaling on the water side raises condensing pressure, which raises compression ratio, which raises discharge temperature. Every degree of excess condensing temperature costs roughly 2–3% in power.
  • Refrigerant charge and leak paths — the shaft seal and the flange joints, not the rotor housing.
  • Control and sensor drift — a skewed temperature sensor makes a healthy machine chase a load that is not there.

All four are visible on a trend log before they are visible on a breakdown. If a site has no trending, the first alarm is the failure.

Specifying one

Give us the duty and the conditions, not a model number: chilled water flow, entering and leaving temperature, ambient or cooling water temperature, glycol concentration if any, and the electrical supply. From that we select rotor size, condenser type and control method, and state the COP at both full and part load.

Our range covers scroll, screw and centrifugal chillers from 20 kW to 1 MW, air or water cooled, built in our own 35,000 m² plant with D1/D2 pressure vessel approval and ISO 9001. If you are comparing a screw machine against a centrifugal at the top of the range, the deciding factor is usually turndown, not full-load efficiency — see chiller and heat exchanger selection.

Frequently asked

How does a screw chiller differ from a scroll chiller? A scroll compressor traps gas between two spirals and compresses it in one orbit, which suits small capacities and gives excellent efficiency at a fixed duty. A screw compressor compresses continuously along helical rotors, which suits large capacities and gives better turndown. Below roughly 150 kW scroll is usually the better buy; above that screw wins on part-load hours.

Why does my screw chiller lose capacity in summer? Air-cooled machines lose capacity as ambient rises because condensing pressure rises. A machine rated at 35°C ambient and run at 43°C can lose 10–15% of capacity. Water-cooled machines are protected as long as the tower is sized for the wet-bulb, not the dry-bulb.

What is normal oil change interval? It depends on run hours and oil type, and the manufacturer’s figure governs. What matters operationally is oil analysis — acidity and moisture, not just hours. A machine on 8,000 hours a year needs sampling more often than the calendar suggests.

Can you supply a screw chiller for -35°C? Yes, with a two-stage or economised arrangement rather than a single-stage machine. See low temperature refrigeration units.