Air cooled screw chiller for laser cutting: sizing two loops, not one

A chiller for a fibre laser is almost never sized correctly by the number the laser is sold under. A 6 kW machine does not need 6 kW of cooling, and it does not need a single loop at a single temperature either. It needs the heat the source actually rejects, at the flow and stability the optics demand, and those two requirements are frequently different.

Getting this wrong does not usually produce a dramatic failure. It produces a laser that derates on hot afternoons, a cutting head that drifts, and a chiller that trips on high pressure every August.

Two loops, two setpoints

Most industrial fibre lasers present two cooling requirements:

  • The source loop — the resonator, the diode stacks and the power supply. Water or a water-glycol mix, typically around 25 to 30 °C, with a tolerance measured in a degree or two. The load is large and relatively steady.
  • The optics and cutting-head loop — the collimator, the focusing optics and the protective window. Often a tighter setpoint, sometimes 22 to 25 °C, and a much tighter stability requirement, because thermal drift in the optics moves the focus.

Some machines use a single loop at one temperature for both, some use a dual-circuit chiller, and a few use a small separate recirculating cooler for the head. The configuration is set by the laser builder, not by preference, so the first question in any selection is which arrangement the machine actually has.

Where the heat actually comes from

A fibre source converts roughly a third to 45 percent of its electrical input into laser light. The rest leaves as heat, and almost all of it goes to the chiller. That means the cooling load is larger than the laser’s rated output, not equal to it:

  • 1.5 kW source — around 4 kW input, roughly 2.5 kW to the chiller, plus the head.
  • 3 kW source — around 8 kW input, roughly 5 kW to the chiller, plus the head.
  • 6 kW source — around 15 kW input, roughly 9 kW to the chiller, plus the head.
  • 12 kW source — around 30 kW input, roughly 18 kW to the chiller, plus the head.

These are indicative figures for sanity-checking a quote, not a specification. The laser OEM publishes a heat rejection figure and a required flow for each loop; that number governs, and any supplier who quotes without asking for it is guessing.

The optics loop adds a small load but a strict one. It is rarely more than a kilowatt or two, and it is the loop that causes the most trouble, because a half-degree of drift at the head shows up as a change in kerf width on thick plate.

Why screw rather than scroll at this size

Below roughly 30 kW of cooling, scroll compressors are the sensible default: simple, quiet, cheap to replace. Above that, and particularly where the machine runs at partial load for most of its life — which a job shop does — a screw compressor holds efficiency better across the turndown range and has fewer moving parts to wear. A laser cell spends a lot of its time at 40 to 70 percent load, so part-load behaviour matters more than the headline capacity.

What matters alongside it is the control: stepless or stepped capacity control that follows the load without short-cycling. A chiller that cycles on and off every few minutes will hold the setpoint badly and wear out the contactors.

Air cooled: the derate and the dust problem

Removing the cooling tower is genuinely attractive for a laser shop: no water treatment, no make-up, no legionella regime, no plume. The cost is that capacity depends on ambient air, and the condenser coil is now a filter for everything in the building.

Two practical consequences:

  • The derate is real. Capacity falls by roughly 2 to 3 percent for every degree of ambient above the design point, and the compressor works harder for what it delivers. Ask for the derate curve at your actual summer ambient and altitude, not at the catalogue condition.
  • Metal dust is the enemy. Laser cutting produces fine oxide and metal dust, and it settles on the coil. A fouled coil raises condensing pressure, cuts capacity and eventually trips the high-pressure switch. Fit a pre-filter or a coarse screen on the air side, and put coil cleaning on a schedule rather than on a breakdown list.

There is also a room-level effect worth designing for: an air cooled chiller dumps its entire heat load into the workshop. In a small hall with poor ventilation that raises the ambient, which derates the chiller, which makes it run longer. Either ventilate the space properly or duct the discharge.

Water quality on the optics loop

The optics loop is not a process water system and should not be treated like one. Requirements are typically deionised or demineralised water with low conductivity, a corrosion inhibitor compatible with the head’s materials, and filtration fine enough to protect the small passages in the optics assembly. Algae, scale and biological growth in an optics loop cause expensive damage, and a clear sight glass is not evidence that the water is clean.

Check conductivity and filter condition at commissioning and at every service interval. If the machine sits idle for weeks, the loop still needs circulation or draining according to the OEM’s instruction.

Hydraulics: pump head, buffer and pipe runs

Three things get undersized on laser chiller installations more than any others:

  • Pump head. The chiller’s internal pump is selected for a short, clean loop. Add 20 metres of pipe, a plate exchanger and a head assembly, and the flow falls below what the laser needs. Required flow is a specification, not a preference.
  • Buffer volume. A small buffer tank stabilises the loop against the pulsed load of a cutting cycle and stops the compressor chasing. It also buys time during a chiller defrost or a compressor unload.
  • Insulation and pipe material. Cold lines sweat. Insulate properly and use materials compatible with deionised water, because DI water is aggressive towards ordinary steel and some copper alloys.

Interlocks that protect the laser

The laser is the expensive part of the installation, and the chiller is what stands between it and a thermal event. As a minimum:

  • Flow switch or differential pressure switch on each loop, wired to the laser’s interlock, not just to a local alarm.
  • Low-level and overtemperature alarms that stop the laser, not merely sound a buzzer.
  • Pump-run confirmation before the laser is permitted to fire.
  • A documented restart sequence after any chiller trip, so nobody clears the alarm and cuts into a cold head.

When water cooled is the better answer

If the shop has three or more lasers, if summer ambient regularly exceeds the chiller’s design point, or if the hall cannot take another 30 kW of heat, a water cooled chiller with a remote dry cooler or tower is usually the better engineering. It costs more to install and it needs water treatment, but it holds capacity through the summer and keeps the heat out of the workspace.

Our air cooled screw chiller range covers the duties described here, the glycol chiller range covers installations that need freeze protection or a sub-zero setpoint, and the engineering services page covers site survey and commissioning support. Send the laser OEM’s heat rejection figure, required flow and setpoint for each loop, plus the summer ambient, and we will size to those rather than to the laser’s nameplate power.