oil cooler heat exchanger pulp and paper

Oil cooler heat exchanger for a pulp and paper mill: duty, fouling and which side the oil goes on

An oil cooler heat exchanger on a paper machine is a small item in the capital budget and a large item in the downtime log. It cools the oil that lubricates gearbox bearings, hydraulic systems and machine drives, and when it fouls, leaks or is undersized, the failure surfaces somewhere expensive: a gearbox rebuild, a felt destroyed by oil, or a stock of paper contaminated by water.

This guide covers the engineering that decides whether the cooler works: what the duty actually is, why oil viscosity changes the whole calculation, which side the oil belongs on, how white water and fibre foul the water side, and the specification points that separate a cooler that lasts from one that is replaced every shutdown.

What an oil cooler heat exchanger does on a paper machine

A paper machine is a long line of rotating equipment running continuously for weeks at a time. Gearboxes on the dryer section, the press section drives, the reel and the winder all reject heat into their oil, and the oil has to be kept within a viscosity band that the bearings were designed around.

The cooler’s job is therefore not to make the oil cold. It is to hold the oil at a temperature where its viscosity is right, which is a control problem as much as a heat transfer problem. Two consequences follow. First, the cooler is usually fitted with a temperature control valve that bypasses part of the flow, so the design duty at full flow is not the duty most of the time. Second, an oversized cooler is not harmless: it over-cools at low load, raises the oil viscosity, and increases the power the system wastes in churning thick oil.

Oil viscosity: why it changes the whole calculation

Heat transfer in oil is dominated by viscosity, and viscosity is strongly temperature dependent. A typical industrial gear oil in the ISO VG 220 or VG 320 range is many times thicker at 40 °C than at 60 °C, and its Prandtl number — the ratio that governs how heat moves through a fluid — is orders of magnitude higher than water’s.

What that means in practice:

  • The oil-side heat transfer coefficient is low compared with water, so the oil side usually controls the overall coefficient and needs the higher velocity.
  • Because viscosity changes with temperature along the cooler, the coefficient changes along the cooler too. A single average value hides a real gradient.
  • Pressure drop rises steeply as the oil cools and thickens, which is why an oil cooler sized only on heat duty can arrive with an impossible pressure drop at cold start.

This is the single most common sizing error on lube oil coolers: the duty is calculated at operating temperature, and the pump is asked to push cold oil through passages sized for hot oil.

If you are sizing a unit now, send us the fluid, the flow rate, the inlet and outlet temperatures you need to hold, and the heat duty in kW. That is enough for us to come back with a sized quotation against your own numbers rather than a catalogue range. The enquiry form is on the contact page, and the selection worksheets on the sizing tools page will give you the flow and duty figures if you do not have them to hand.

Where the heat comes from: building the duty

The heat rejection of a gearbox or hydraulic system is not a catalogue number. It is the difference between the power going in and the power coming out as useful work, plus whatever the machine’s own losses add.

A defensible way to build the duty:

  • Start from the drive power and the efficiency at the operating point. The losses are the heat, and for a gearbox at part load the loss fraction is usually worse than at rated load.
  • Add hydraulic system losses separately: pressure drop across valves and relief flow converts directly to heat in the oil.
  • Account for the machine’s thermal mass and the duty cycle. Continuous operation reaches steady state; a machine that stops and starts does not.
  • Allow for summer cooling water. Water at 32 °C in August gives a much smaller temperature difference than water at 18 °C in March, and the cooler has to work in August.

Where measured data exists — oil temperature rise with the cooler valved out, or a heat balance on the gearbox — it beats any estimate. On an existing machine, that measurement is the cheapest engineering available.

Which side the oil goes on

For a shell and tube oil cooler the conventional arrangement puts oil in the shell and cooling water in the tubes, and there are good reasons for it.

  • Fouling. Water is the dirtier stream in a paper mill, and the tube side is the side that can be cleaned by brushing or by pushing a cleaner through. Putting water in the tubes keeps the cleaning problem where cleaning is possible.
  • Velocity. Water can be run at a higher velocity in tubes without excessive pressure drop, which keeps the water-side coefficient high and resists deposition.
  • Pressure. Oil systems are usually low pressure; water systems can be higher. Keeping the higher pressure in the tubes is the safer arrangement for cross-contamination, because a leak then goes water-into-oil rather than oil-into-water.

The exception is a plate heat exchanger, where both streams are in narrow passages and the choice is made on pressure drop and cleanability rather than on principle. Plates pack a large area into a small frame and are excellent where the water is clean; they are a poor choice where the water carries fibre.

Fouling: white water, fibre and the water side

Cooling water in a paper mill is rarely clean. It may be river water, clarified water, or a white water stream reused from the process, and each carries its own problem.

  • Fibre and fines mat on tube surfaces and in low-velocity zones, forming an insulating layer that grows until the cooler cannot hold temperature.
  • Scale from hard make-up water deposits on the hottest surface, which is the oil-side wall.
  • Biological growth in lukewarm water plugs passages, particularly where flow is intermittent.

Design responses that work: keep water velocity above the threshold that resists settling, avoid dead pockets in the water-side headers, specify a fouling allowance that reflects the actual water rather than a clean-water assumption, and provide isolation valves and drain points so the cooler can be cleaned without a shutdown of the whole machine.

Pressure drop on the oil side

Oil-side pressure drop is the constraint that decides whether a compact cooler is usable. The pump has a fixed head available, and the cooler has to fit inside it along with the piping, the filter and the control valve.

Three levers control it: passage geometry, number of passes, and oil temperature at the design point. More passes raise velocity and the heat transfer coefficient but raise pressure drop roughly with the square of velocity. The practical approach is to fix the allowable pressure drop first, then size the cooler inside that limit, rather than to size on duty and discover the pressure drop afterwards.

Cold start deserves its own check. Oil at ambient in a cold mill can be several times more viscous than at operating temperature, and the resulting pressure drop may exceed the relief setting before the oil warms. A warm-up bypass, or a control valve that routes oil around the cooler until temperature rises, solves it.

Tube failure and cross-contamination

The failure that matters most is a tube leak, because the consequence is not a loss of cooling but a contamination event. Water in oil destroys bearing surfaces; oil in water shows up as a paper defect long before anyone finds the cooler.

Common causes:

  • Vibration from flow-induced excitation, which fatigues tubes at the baffle crossings. The fix is baffle spacing and support that keeps the natural frequency away from the excitation.
  • Thermal expansion restrained by a fixed tubesheet, which loads the tube-to-tubesheet joints every time the unit heats and cools.
  • Corrosion from chlorides in the cooling water, particularly where flow is low and deposits hold chlorides against the metal.
  • Erosion at tube inlets where water velocity is highest and the entrance is not chamfered.

Where the consequence of cross-contamination is severe, the design answer is a double tubesheet or an internal leak-detection path, so that a failed joint shows up as a visible weep rather than as water in the oil sump.

Materials: tubes, tubesheet and chlorides

Material selection on the water side is a chloride question first and a temperature question second. Stainless steels that are entirely suitable in fresh water can suffer chloride stress corrosion cracking in warm, concentrated conditions, and the concentration happens exactly where deposits sit.

  • Carbon steel is adequate for clean, treated water with a corrosion inhibitor programme, and it is the cheapest option on the oil side.
  • Stainless steel tubes suit most mill water and are the usual upgrade when carbon steel life is short.
  • Duplex or higher grades where chlorides and temperature are both high, or where the water is brackish.
  • Copper alloys are effective thermally but are sensitive to ammonia and to sulphide, both of which appear in some mill water circuits.

On the oil side, carbon steel is normal. The point worth insisting on is that the tubesheet material and the tube material are compatible with each other and with the water, because the tubesheet is where galvanic problems concentrate.

Cleaning: in place or pull the bundle

The cooler has to be maintainable, and maintainability is decided at the specification stage. Three provisions make the difference.

  • Isolation and drains on both sides, so the unit can be taken out of service without draining the machine.
  • Removable bonnets or a bolted channel on the water side, giving straight access to the tube ends for brushing.
  • Space to withdraw the bundle if the design allows it. A cooler installed tight against a wall cannot be pulled, and that constraint is discovered at the worst possible moment.

Chemical cleaning works for scale and biological growth but does nothing for a fibre mat. Mechanical cleaning works for fibre but not for hard scale. A mill usually needs both capabilities, which is another argument for water in the tubes.

Sizing an oil cooler heat exchanger without oversizing it

Oversizing looks safe and is not. It costs capital, it over-cools at low load, it can drive the control valve into a permanently throttled position where it hunts, and it makes the pressure drop budget harder rather than easier.

A sound sequence is:

  • Fix the allowable pressure drop on both sides from the pumps that exist.
  • Fix the maximum cooling water temperature in the worst month.
  • Choose the approach temperature you are willing to accept, remembering that a small approach means a large area and that the last few degrees are the expensive ones.
  • Size for the duty at that approach, then check the low-load case for over-cooling and control stability.
  • Check the cold-start pressure drop with oil at ambient.

If the resulting unit is larger than the space allows, the honest options are a higher water flow, a lower approach specification, or accepting a higher oil temperature at peak — in that order of preference. Compressing the area and hoping is not one of them.

Specification checklist

What a supplier needs in order to quote a cooler that fits the machine:

  • Oil grade and the operating temperature range, not just a single figure.
  • Oil flow rate and allowable pressure drop.
  • Heat duty, or the data to calculate it.
  • Cooling water source, flow, maximum temperature and analysis.
  • Design pressure and temperature on both sides.
  • Material requirement for tubes, shell and tubesheet.
  • Connection sizes and orientation, and the space available for maintenance.
  • Any requirement for leak detection or double tubesheet.

Given those, the thermal design is arithmetic and the mechanical design follows the applicable pressure vessel code. Our shell and tube and pressure vessel range covers this class of cooler, and where the duty is better served by a compact unit the spiral and compact options are worth comparing on fouling behaviour rather than on footprint alone.

Reference: API Standard 614, Lubrication, Shaft-Sealing, and Control-Oil Systems and Auxiliaries for Petroleum, Chemical and Gas Industry Services — api.org.