air cooled screw chiller chemical plant

Air Cooled Screw Chiller for a Chemical Plant: Selection for Corrosive and Classified Sites

Why Chemical Plants End Up With Air Cooled Screw Chillers

A chemical plant usually decides on an air cooled screw chiller for reasons that have nothing to do with efficiency. Cooling towers need make-up water, treatment chemicals, a blowdown route and a plume that the neighbours can see. In a plant where the water is already committed to process, where the atmosphere is corrosive enough to eat a galvanised tower in five years, and where a visible plume is a planning objection, the air cooled machine wins by default.

The trade is real and it should be stated plainly: an air cooled condenser rejects heat at the dry-bulb temperature, not the wet-bulb, so a machine in a hot climate condenses 10 to 15 K higher than a water cooled equivalent and pays perhaps 20 to 30 percent more compressor power for the same duty. What you buy with that power is independence from water, no tower maintenance, no chemical treatment programme, and the ability to put the chiller wherever the pipe run is shortest.

This guide is about the selection work that has to happen before an air cooled screw chiller for a chemical plant is ordered — because the chemical plant is the hardest ordinary application for one. The loads are batchy, the atmosphere attacks the coil, and half the site may be a hazardous area.

Define the Duty Properly Before Anything Else

Chemical plant cooling loads are rarely one number. A single chiller often serves three different kinds of load, and the selection has to satisfy all of them at the same time.

Load typeTypical shapeEffect on selection
Reactor jacket coolingBatch, step changes of 30–100%Needs fast turndown and a buffer tank
Condenser dutyContinuous, ambient-sensitiveSets the base load and the condensing temperature
Analyser and sample coolingSmall, absolutely continuousDrives redundancy, not capacity
Tank farm and drum coolingSeasonal, slowCan be met by a separate circuit
Utility and HVACDaytime-peakedUsually the load that sets the summer maximum

Two numbers decide most of the capital cost: the peak coincident load and the minimum turndown. A plant that quotes only a peak figure will get a machine that cycles, and a screw compressor that cycles is a screw compressor that wears its slide valve and its unload solenoids.

The Temperature Regime: Where the kW Actually Goes

Compressor power is a function of the lift between evaporating and condensing temperature, and both ends move. On the evaporator side, every 1 K reduction in evaporating temperature costs roughly 2.5 to 3.5 percent of capacity and adds a similar share of power. On the condenser side, every 1 K rise in condensing temperature costs 2 to 3 percent of power.

Leaving chilled fluidEvaporating tempCapacity indexPower index
12 °C7 °C10894
7 °C2 °C100100
0 °C−5 °C91108
−10 °C−15 °C80119

Indices are relative to a 7 °C leaving temperature at the same ambient, and they are indicative rather than exact — but the direction is not negotiable. Ask for 0 °C supply when 7 °C would do and you buy a bigger machine that runs harder forever. Chemical plants ask for low temperatures more often than they need them, usually because one cold trap somewhere in the process wants it.

Ambient Design: The Coil Does Not Know It Is a Design Day

Air cooled condensers are rated at a stated ambient. A machine rated 500 kW at 35 °C delivers roughly 460 kW at 43 °C and about 430 kW at 48 °C, because the condensing temperature has to climb to keep the same approach to a hotter air stream. If your site records 44 °C once a summer and the process trips when the chilled fluid rises 2 K, that once-a-summer event is the design case.

Three practical responses, in order of cost:

  • Rate at the real ambient and accept a larger machine that runs lightly for eleven months of the year.
  • Add adiabatic pre-cooling on the worst weeks — a small water consumption for a large capacity recovery, but it reintroduces water, scale and Legionella management.
  • Accept a floating chilled-fluid temperature and let the process tolerate a warmer utility on hot afternoons.

Floating condensing pressure is worth real money on an air cooled machine and is under-used. Where the refrigerant and the expansion device allow it, letting the condensing temperature fall with ambient in cool weather recovers 8 to 15 percent of annual energy at no capital cost.

Corrosion: The Chemical Plant Atmosphere Is the Real Specification

A standard air cooled chiller has aluminium fins on copper tubes. That combination is fine in a clean inland site and unacceptable in a chemical plant. Hydrogen sulphide, chlorine, hydrogen chloride mist, ammonia slip and coastal salt all attack the fin-to-tube bond first, then the aluminium fin itself, and the failure mode is silent: the coil loses capacity gradually as the bond degrades, and nobody notices until the machine cannot hold setpoint on a hot day.

Site atmosphereCoil specificationReason
Clean inlandAluminium fin, copper tubeStandard; lowest cost
Coastal, salt mistEpoxy-coated aluminium finBarrier on the fin surface
H₂S or chlorine presentHeresite or epoxy fin, coated tubeCopper sulphide and chloride attack
Acid mist, HClStainless tube, coated finCopper is not defensible
Ammonia slipCoated copper, not bareStress corrosion of the tube

Specify the coating by test, not by trade name. Ask for salt-spray hours to ASTM B117 and for a coating thickness in micrometres, and ask what happens at the fin edges where the coating is thinnest. A coil that is coated only on the flat of the fin and bare at the louvre edge will corrode from the edge inward.

The frame and casing matter as much. A painted mild-steel frame in an acid atmosphere will show rust at the bolt heads within two years. Stainless casing, hot-dip galvanised after fabrication, or a properly specified coating system are all defensible; a thin shop coat is not.

Hazardous Areas and Refrigerant Choice

If the chiller sits inside a classified area, the whole machine becomes a documentation exercise. The two viable approaches are to place it outside the zone — usually the cheapest answer by a wide margin — or to specify a machine suitable for the zone.

  • Zone 2 with purge and pressurisation to IEC 60079-2 is the common route for a compressor package. It requires clean instrument air, a purge cycle before start, and pressure monitoring that trips the machine on loss of purge.
  • Increased-safety motors and Ex-rated instrumentation cover the electrical side but not the refrigerant leak itself.
  • Refrigerant selection interacts with the zone. A2L fluids such as R1234ze and R32 carry charge limits and ventilation requirements under EN 378; A3 fluids such as propane are usually excluded from plant rooms in chemical facilities regardless of how good the efficiency looks on paper.

Where the process already has an ammonia refrigeration system, an ammonia chiller can make sense — but it brings the machinery room requirements, the detection system and the ammonia gasket and material rules with it. For a stand-alone utility chiller in a chemical plant, an HFC or HFO machine with a modest charge is usually the simpler compliance story.

Glycol, Brine and the Capacity You Lose to It

Any chiller that must run below about 4 °C, or that sits outdoors in a freezing climate, needs antifreeze in the secondary loop. Glycol reduces specific heat, raises viscosity and lowers the heat transfer coefficient, so the machine has to be rated on the mixture, not on water.

ConcentrationPropylene glycol freezeEthylene glycol freezeCapacity penalty
20%−7 °C−9 °C3–5%
30%−13 °C−15 °C6–9%
40%−21 °C−24 °C11–15%
50%−33 °C−37 °C16–22%

Propylene glycol is the right choice wherever a leak could reach product, drainage or people. Ethylene glycol transfers heat better and is cheaper; it is also toxic, and in a chemical plant the leak path is never as controlled as the P&ID suggests. Whatever the choice, the loop needs a inhibitor package maintained on a schedule and a refractometer reading recorded monthly — a glycol concentration that drifts down in winter is a burst evaporator waiting for the first cold night.

Part-Load Behaviour: Where the Money Is Made or Lost

A screw compressor with a slide valve unloads steplessly down to roughly 25 percent of capacity; below that it has to cycle or run on hot-gas bypass, both of which are inefficient and both of which wear the machine. A variable-speed drive extends useful turndown to 15 percent or lower and, more importantly, matches capacity to load continuously instead of sliding in and out.

For a chemical plant, the load profile usually justifies the drive. Batch reactors mean long stretches at 40 percent load; a fixed-speed screw at 40 percent is running at a poor part-load ratio, while a VSD machine follows the load. Two smaller compressors in separate circuits also beat one large machine on a batchy load, and they give you N+1 without buying a second chiller.

Ask for the part-load table, not the single full-load COP. A machine with an excellent full-load number and a poor 40 percent point is the wrong machine for a batch plant.

The Heat Exchanger Scope Inside the Chiller

The evaporator and condenser inside a screw chiller are heat exchangers in their own right, and their specification matters as much as the compressor.

  • Evaporator: shell and tube, usually flooded, with the water in the tubes and refrigerant in the shell. Tube material and water velocity determine whether it survives twenty years or eight.
  • Condenser: the air cooled coil, with subcooling circuit and, on larger machines, a separate subcooler.
  • Oil cooler: often a small brazed plate or shell and tube unit on the same water circuit — check that it does not steal flow from the evaporator at low load.
  • Desuperheater: an optional recovery section that takes the discharge gas before the coil and produces 45–60 °C water. On a plant with a hot-water demand this is the cheapest efficiency measure available, and it also lowers the coil duty.

If the plant has a genuine 50 °C hot-water requirement, a desuperheater can recover 10 to 20 percent of the rejected heat. Our notes on recovering waste heat from cooling plant into a district or process heating network set out how the temperature tiers stack up; the same logic applies inside a chemical site.

Water Side, Filtration and the Closed Loop

The chilled-water loop is usually closed, which people read as “no water treatment needed”. It is not. A closed loop with a make-up connection and an open expansion tank will grow bacteria, collect debris and corrode from the inside. Specify a 40-mesh strainer on the return, a side-stream filter, and a corrosion inhibitor with quarterly testing for iron, copper and conductivity.

Flow matters too: keep the evaporator tube velocity between about 1.0 and 2.0 m/s. Below that, fouling accelerates; above it, erosion-corrosion at the tube inlet becomes the failure mode. If the process needs a wide flow range, a two-pass evaporator with a lower design velocity is usually the safer compromise.

Controls, Redundancy and the Things That Stop a Plant

A chiller is a utility, and a utility that stops takes the plant with it. Three items earn their cost:

  1. Dual refrigerant circuits on one frame, so a compressor fault leaves half the capacity running.
  2. Remote monitoring with alarm escalation, so a low-pressure trip at 02:00 reaches somebody.
  3. A buffer tank sized for the largest batch step — typically 10 to 20 minutes of peak flow — so a reactor dump does not trip the machine on low leaving-water temperature.

RFQ Data Package: What to Send

A quotation built on “we need 500 kW” will be replaced by a quotation built on real data, at a different price. Send the following and the selection becomes deterministic.

  • Peak and minimum coincident load, in kW, with the profile over a typical day.
  • Chilled fluid: water or glycol, concentration, flow rate, entering and leaving temperature.
  • Design ambient dry bulb, and the highest recorded ambient on site.
  • Site atmosphere: which corrosive species are present and at what concentration.
  • Hazardous area classification drawing, or a statement that the chiller will sit outside the zone.
  • Refrigerant preference or restriction, and any corporate phase-down policy.
  • Electrical supply, voltage, frequency, and whether a VSD is required.
  • Acoustic limit at the nearest sensitive receptor, in dB(A) at a stated distance.
  • Water-side design pressure and allowable pressure drop.
  • Documentation required: material certificates, ATEX certificates, FAT, and the language of the O&M manual.

Selection then works from the load and the ambient inward. The evaporator and condenser selection logic for chillers covers how the heat exchanger scope is sized once those numbers are fixed, and the air cooled heat exchanger and dry cooler range covers the coil side where the condenser is being specified separately.

Erection and Commissioning Checks

Air cooled machines fail at commissioning more often than in service, and almost always for one of four reasons: recirculation of hot air back into the coil, insufficient clearance to a wall, a glycol loop with air trapped at the high point, or a coil that was damaged in transit and never inspected.

Check the clearance to any obstruction against the manufacturer’s figure measured from the coil face, not the casing. Confirm that units in a row do not discharge into each other. Vent the loop at the highest point and repeat after the first week. And walk the coil with a light behind it before signing the delivery note — bent fins are cosmetic, but a crushed tube end is not.

Next Step

If you are specifying an air cooled screw chiller for a corrosive or classified site, send the load profile, the ambient and the atmosphere data through our engineering enquiry form. We will come back with a selection, the coil specification that suits the atmosphere, and a heat exchanger duty sheet you can check independently — Zhenggong builds to D1/D2 pressure vessel requirements under ISO 9001 and ISO 14001, documented on the certification page.