transformer oil cooler selection

Transformer Oil Cooler: ONAF and OFAF Selection and Sizing

What a Transformer Oil Cooler Actually Has to Do

A transformer oil cooler removes the heat that the core and windings generate, and it does so through a fluid that is also the insulation. That dual role is what separates it from every other oil cooler on a plant: the oil temperature cannot simply be driven down for thermal comfort, because the cooler’s job is to keep the top-oil and hot-spot temperatures inside the limits that preserve paper insulation life, at the lowest auxiliary power and the smallest footprint the site allows.

The consequence is that selection starts with the cooling class on the nameplate, not with a heat duty. A unit rated 20 MVA ONAN / 25 MVA ONAF has two different heat rejection requirements depending on which fans are running, and a retrofit that adds cooling capacity without respecting the winding temperature limits can raise the rating on paper while shortening insulation life in practice.

Read the Cooling Class Before Sizing Anything

IEC 60076-2 codes cooling in four letters: internal coolant, its circulation, external coolant, its circulation. In practice five combinations cover almost everything.

ClassMeaningTypical rating effectWhere it is used
ONANOil natural, air natural100% (base rating)Distribution units and small power transformers; silent, no auxiliaries
ONAFOil natural, air forced125–133% of ONANThe standard step-up for a tank that cannot grow; fans on the radiator bank
OFAFOil forced, air forcedUp to 166% of ONANLarge power transformers where a pumped oil-to-air cooler replaces radiators
ODAFOil directed, air forcedHighest capacityVery large units with directed winding ducts; pump and cooler package
OFWFOil forced, water forcedHighest per unit volumeIndoor substations, hydro stations, sites with no room for air coolers

Two things follow from that table. First, the fan and pump auxiliaries are part of the rating, so a cooler that loses a fan does not lose a percentage point of capacity — it drops the transformer back to its ONAN or ONAF rating, which may be 25% lower. Second, the cooler has to be sized for the highest class the transformer will run in, and for the ambient at which that class was declared.

Heat Balance: Where the Losses Come From

The cooler duty equals total transformer losses at the load being carried — no more, no less. For a modern oil-immersed unit the split is roughly:

  • No-load (core) loss: 0.15–0.30% of rated power, constant whenever the unit is energised.
  • Load (copper) loss: 0.6–1.0% of rated power at full load, falling with the square of the load factor.
  • Stray and eddy losses: a few percent of the total, concentrated in the tank walls and structural steel near the bushings.

So a 10 MVA transformer with 1.0% total losses rejects about 100 kW at full load, and about 55 kW at 70% load. That turndown matters: the cooler should be controllable in steps, because running every fan at 55 kW of duty wastes auxiliary power for 80% of the year.

Sizing an Oil to Air Cooler

  1. State the design ambient. 40 °C is the usual industrial design condition; 45–50 °C for tropical and desert sites. The IEC temperature-rise limits assume a 40 °C maximum ambient, so a site at 48 °C needs the cooler oversized or the rating reduced.
  2. Fix the oil temperatures. Top-oil limit 55–60 K rise, so at 40 °C ambient the oil enters the cooler at up to 95 °C on a 55 K design and leaves 10–15 K cooler. Mean oil temperature, not top-oil, drives the calculation.
  3. Calculate LMTD. Oil in at 82 °C, oil out at 67 °C, ambient 40 °C gives an LMTD of 34 K — not the 42 K that subtracting the mean oil temperature from ambient would suggest.
  4. Select U on a stated basis. Forced-draught fin-tube banks with 8–11 fins per inch run 25–40 W/m²·K referred to bare tube area at 2.5–3.5 m/s face velocity. Natural-convection radiators behave as 8–12 W/m²·K. The two numbers are not interchangeable, and quotations that do not say which basis they use cannot be compared.
  5. Convert to surface. 100 kW at U = 30 W/m²·K and LMTD 34 K needs 98 m² of bare-tube area, plus 10–15% fouling and manufacturing margin.
  6. Check the oil velocity. 1.5–2.5 m/s in the tubes or element passages. Below 1 m/s the oil side coefficient collapses and sludge settles; above 3 m/s the pressure drop starts to matter to the pump.
  7. Size the auxiliaries. Fans of 1.5–3 kW each for a cooler of this size, on a two-stage or VFD control from the winding temperature indicator, drawing well under 1% of transformer rating when running.

Radiator Bank or Forced Cooler?

The choice is usually made for you by the tank, but it is worth stating the trade honestly.

Radiator bank (ONAN/ONAF)Oil-to-air cooler (OFAF)
FootprintLarge, but spreads along the tankCompact, can be remote-mounted
AuxiliariesFans only for ONAFPumps plus fans, both with standby
MaintenanceFin cleaning, gasket leaks at the top flangeFan and pump bearings, oil-side cleaning, valve sequencing
Failure modeGradual loss of capacityPump trip reverts the unit to a much lower rating, immediately
Best fitUp to about 60 MVA, outdoor, unattendedAbove that, or where space and noise are constrained

For retrofits, adding ONAF fans to an existing radiator bank is the cheapest capacity gain available — 25–33% for the price of fans and a control panel. Replacing radiators with a pumped cooler gives more, but needs tank nozzle work, a new oil circuit and a foundation, and it changes the unit’s cooling class on the nameplate, which the insurer and the network operator will both want documented.

Ambient, Altitude and Enclosure Derating

  • Ambient above 40 °C: each 1 K above the declared ambient reduces permissible loading by roughly 1%, unless the cooler is oversized to compensate.
  • Altitude above 1,000 m: air density falls, mass flow falls, and air-cooled capacity falls with it — allow about 1% per 100 m, and more for natural-convection radiators.
  • Enclosed or vault installation: the cooler is only as good as the ventilation. A 100 kW cooler in a room with 20 m³/s of airflow needs an inlet and outlet that actually pass 20 m³/s; louvre free area is typically 50% of the opening.
  • Recirculation: coolers mounted in a row, or against a wall, pull their own hot discharge back in. Two metres of clear space above and a discharge velocity above 4 m/s prevents most of it.

Oil Chemistry Changes the Cooler

Mineral oil per IEC 60296 is the default and the cheapest. Natural ester per IEC 62770 has a fire point above 300 °C and is increasingly specified for urban and environmentally sensitive substations, but its viscosity at low temperature is much higher and its pour point is around −18 °C. The practical effects on the cooling circuit are real: a pump selected for mineral oil will be under-sized for natural ester in a cold start, the cooler needs more surface for the same duty at the same flow, and every elastomer in the circuit has to be checked for compatibility. Synthetic ester costs more and solves the cold-start problem with a pour point near −50 °C.

One warning worth repeating: gaskets and paints that have been fine for thirty years in mineral oil can swell, soften or leach in ester. A cooler retrofit that changes the fluid without changing the seals is a leak waiting for the first hot day.

Installation and Maintenance Points That Get Missed

  • Coating class. Coastal and offshore substations need C5-M. A standard paint system on a fin-tube bank at 500 m from the sea fails at the fin collar first, where it cannot be repainted.
  • Fin cleaning every 12–24 months in dusty or agricultural locations. Pollen and cottonwood block a fin pack completely in one season, and the first symptom is a top-oil alarm on a hot afternoon.
  • Noise. Fan noise at the nearest dwelling is often the binding constraint on a substation cooler, not thermal duty. Low-speed large-diameter fans move the same air more quietly than small high-speed ones.
  • Valves and isolation. A cooler that cannot be isolated cannot be maintained without an outage. Butterfly valves on both oil connections, with the bypass blind in place.
  • Monitoring. Winding temperature indication with alarm and trip stages, plus dissolved gas analysis at the normal interval. Rising top-oil at constant load and constant ambient means a fouled cooler or a failing pump, not a failing transformer.

Specification Checklist

  1. Transformer rating in each cooling class, and the ambient at which those ratings are declared.
  2. Total losses at rated load, and the loss curve for the load profile the unit will actually see.
  3. Oil type, volume, viscosity at the minimum site temperature, and the pump curve that follows from it.
  4. Cooler duty, oil inlet and outlet temperatures, and the LMTD basis.
  5. U value with the area basis stated, plus the fouling allowance.
  6. Fan and pump quantities, standby arrangement, and control stages from the winding temperature indicator.
  7. Coating system, corrosion class and expected service life at the site’s distance from the coast.
  8. Noise limit at the boundary, and the fan selection that meets it.
  9. Certification, pressure test records and the documentation the network operator requires.

Zhenggong builds fin-tube oil-to-air banks and oil-to-water shell-and-tube units in a 35,000 m² facility in Shandong, working to D1/D2 pressure vessel certification and ISO 9001 and ISO 14001 systems. The air-cooled heat exchanger and dry cooler range covers the fin-tube geometry used for transformer and oil cooling duty, including coastal coating specifications.

The sizing logic for the oil side is shared with industrial hydraulic circuits, set out in the guide to hydraulic oil cooler selection, which covers viscosity, flow and air-versus-water trade-offs in more detail. Substation and utility applications are grouped on the application pages.

If the transformer rating and the site ambient are known, send them to our engineering team with the oil type and the space available. We will return a cooler selection with the surface area, the fan and pump duty, and the derating curve at the site’s maximum ambient, so the choice between radiator and forced cooler is made on numbers rather than on habit.