Where the Exchangers Sit in an Ammonia Water Absorption Chiller
An ammonia water absorption chiller replaces the compressor of a vapour-compression machine with a thermal compressor: a generator that boils ammonia out of a concentrated solution, an absorber that takes it back, and a pump that moves perhaps 2% of the electrical power a compressor would need. The prize is cooling driven by steam, hot water, exhaust gas or geothermal brine instead of electricity, at evaporator temperatures down to −40 °C where lithium bromide machines cannot go at all.
Every one of those steps happens in a heat exchanger, and the selection of those exchangers decides the cycle COP as much as the thermodynamics does. This guide covers the six duties, the pressures they run at, the materials that survive ammonia, and the specification data a fabricator needs to quote a machine that will actually hold its rating.
The Six Duties and What Each One Demands
A single-effect ammonia water machine has a generator, a rectifier or analyzer, a condenser, an evaporator, an absorber and a solution heat exchanger. They run at two pressure levels — roughly 12–16 bar on the high side and 1–3 bar on the low side — and the pressure difference is what makes the solution heat exchanger a pressure-vessel problem rather than a plumbing one.
| Duty | Hot side | Cold side | Typical pressure | Exchanger type |
|---|---|---|---|---|
| Generator | Steam 0.3–0.8 MPa, hot water 90–160 °C, or flue gas | Rich NH₃/H₂O solution boiling | 12–16 bar | Kettle, falling film or forced circulation shell and tube |
| Rectifier / analyzer | Vapour with water carry-over | Reflux liquid | 12–16 bar | Small shell and tube or plate-fin |
| Condenser | Ammonia vapour | Cooling water 30–35 °C or air | 12–16 bar | Shell and tube, or air-cooled fin fan |
| Evaporator | Process fluid or brine | Ammonia boiling at −40 to +5 °C | 1–3 bar | Flooded shell and tube, or plate with distributor |
| Absorber | Lean solution | Cooling water | 1–3 bar | Shell and tube with tube-side water, or sprayed coil |
| Solution heat exchanger | Hot lean solution from generator | Cold rich solution from pump | Shell 12–16 bar, tubes 1–3 bar | Shell and tube, or welded plate |
The duty split follows the COP. Take a 1,000 kW machine at COP 0.55 on a −25 °C evaporator: generator input is about 1,820 kW, and the condenser plus absorber must reject roughly 2,800 kW between them, with the absorber carrying the larger share — typically 1.3–1.5 times the condenser duty, because it removes both the absorption heat and the sensible heat of the incoming vapour. That rejection load, not the cooling capacity, sizes the cooling tower.
Materials: Ammonia Punishes the Obvious Choices
Ammonia plus water attacks copper, all copper alloys including cupronickel and bronze, and zinc coatings. Aluminium is also out. This rules out the brazed copper plate pack and the copper-nickel tube bundle that would be the cheap answer in a water-to-water duty.
- Carbon steel for shells, and for tubes where the fluid is clean and velocity is controlled. It is the standard choice for the generator, condenser and absorber shells.
- Stainless steel 304 or 316L for solution-wetted parts at higher velocity, for the rectifier, and anywhere erosion-corrosion is a risk.
- No galvanising anywhere in the circuit, including bolts and supports. Zinc in an ammonia environment is a stress-corrosion problem waiting for a wet start-up.
- Stress-relieve welds on high-strength carbon steel components; ammonia stress corrosion cracking needs oxygen and residual stress, and the design should not supply the second one.
- Gaskets and seals: PTFE, EPDM and butyl are generally acceptable, nitrile less so at higher ammonia concentrations, and every elastomer needs checking against the actual solution strength and temperature.
The Solution Heat Exchanger Is Where the COP Is Won
Between the absorber and the generator sits a recuperator that preheats the rich solution on its way up using the hot lean solution coming down. It transfers no heat to the process and produces no cooling, which is exactly why it gets underspecified — and exactly why it matters.
Every kelvin recovered there is a kelvin the generator does not have to supply. At an effectiveness of 0.75, the recuperator typically returns 20–30% of the generator duty, lifting the cycle COP by 15–25% compared with an unrecuperated machine. Effectiveness of 0.70–0.85 is the practical band; pushing to 0.90 means a very large, very expensive unit with a tiny marginal gain, because the two streams approach each other and the LMTD collapses.
Two design points are worth insisting on. First, the pressure difference across this exchanger is the full cycle pressure ratio — 10–14 bar — so it must be built as a pressure vessel with a tube sheet designed for that differential, not as a plate pack chosen on temperature alone. Second, a leak between the two sides does not create a safety hazard, but it does quietly destroy the concentration profile in the machine and cost 5–10% of capacity; a welded or double-tube-sheet construction removes the risk at modest cost.
The Generator: Matching the Heat Source You Actually Have
The generator is the largest and most expensive exchanger in the machine, and its design is dictated by the heat source rather than by the refrigeration duty.
Steam and direct firing
Steam at 0.3–0.8 MPa gives a large ΔT and a compact generator, usually a kettle or falling-film shell and tube with the solution boiling on the tubes. Direct-fired units use a similar shell with a burner and a larger radiant section. Both handle solution concentrations up to 40–50% ammonia in water and must cope with the frothing that comes with boiling a foamy solution — hence vapour disengagement space above the tube bundle, typically 0.8–1.2 m of shell height, and a mesh pad or centrifugal separator before the rectifier.
Hot water
Hot water at 90–120 °C is the common waste-heat case, and it is where COP falls. With a 90 °C source condensing at 35 °C the generator pinch becomes the binding constraint, and the machine may only manage 0.4–0.5 COP at a −10 °C evaporator. A falling-film generator is the right answer here: it needs a smaller driving ΔT than a flooded kettle for the same duty, because it does not have to overcome the hydrostatic head of a deep liquid column.
Flue gas and geothermal brine
Dirty or scaling sources belong on the tube side of a finned or bare-tube bundle with a generous fouling allowance and a cleanable arrangement. Geothermal brine at 120–150 °C will scale, so design the generator for a 0.0003–0.0005 m²·K/W fouling factor and provide a chemical cleaning connection rather than relying on mechanical access that does not exist inside a pressure vessel.
Absorber and Condenser: The Rejection Side Limits Everything
Cooling water at 30–35 °C sets the condensing pressure, the absorber exit concentration and therefore the whole cycle. A 3 K rise in cooling water temperature can cost 4–6% of capacity, which is why absorption machines are specified with a cooling water temperature rather than a range.
- Approach in the absorber: 3–5 K between the solution and the cooling water. Tighter than that and the exchanger area grows faster than the COP gain.
- Cooling water velocity: 1.0–1.8 m/s in the tubes. Below 0.9 m/s the fouling rate climbs steeply; above 2 m/s erosion-corrosion appears in carbon steel.
- Air-cooled condensers are possible and are used where water is scarce, but a 45 °C ambient pushes condensing pressure to 18–20 bar and cuts capacity by 10–15% against the water-cooled rating. Allow 15–20% more area and specify the fan power into the parasitic load.
- Absorber internals matter more than the surface area: a sprayed or falling-film arrangement with good liquid distribution outperforms a flooded bundle of the same area by a wide margin.
Ammonia Water vs Lithium Bromide vs Electric, Honestly
| Criterion | NH₃/H₂O absorption | LiBr absorption | Electric chiller |
|---|---|---|---|
| Evaporator range | +5 to −40 °C | +5 °C and above | +10 to −40 °C |
| Single-effect COP | 0.50–0.65 | 0.65–0.75 | 4.5–6.5 (electrical) |
| Driving heat | 90–180 °C steam, hot water, gas, brine | 88–95 °C hot water, steam | Electricity only |
| Operating pressure | 12–16 bar high side | Vacuum, 6–8 mbar | 10–18 bar |
| Refrigerant hazard | Toxic, flammable, needs detection and ventilation | Corrosive to steel, crystallisation risk | Depends on refrigerant |
| Materials | Carbon steel and stainless; no copper | Stainless and copper alloys | Copper alloys standard |
| Best fit | Industrial freezing, cold storage, waste-heat driven plants | Comfort cooling from hot water | Anywhere electricity is cheap and reliable |
The single-effect COP of 0.55 looks poor against an electric chiller until you price the input. Where the driving heat is otherwise wasted — turbine exhaust, digester gas engine jacket water, geothermal brine — the marginal cost of that heat is close to zero and the comparison is against the electricity the chiller would have consumed, not against the fuel the boiler burned.
Specification Checklist for the Exchanger Package
- Cooling capacity, evaporator temperature and the process fluid with its flow and allowable ΔP.
- Heat source: medium, temperature in and out, flow, and cleanliness. This decides the generator type.
- Cooling water temperature and flow, plus the maximum wet-bulb if an air-cooled condenser is intended.
- Solution concentration range at generator outlet and absorber outlet, with the property source used.
- Design pressure and temperature for both pressure levels, and the hydro test pressure required.
- Material specification per component, with a statement that no copper alloy or galvanised item enters the circuit.
- Fouling factors per duty, and which side is cleanable.
- Certification: D1/D2 pressure vessel documentation, material certificates, NDT records and a third-party inspection option for export projects.
Build the Machine Around Exchangers That Hold Their Rating
Absorption machines are unforgiving of a heat exchanger that is 10% short on area, because the shortfall appears as a permanent capacity deficit rather than as a higher utility bill. The generator, absorber and recuperator have to be sized from a closed cycle balance, built in the right materials, and documented to a pressure vessel code that the buyer’s inspector will accept.
Zhenggong manufactures shell and tube and plate exchangers for absorption and compression refrigeration duty under D1/D2 pressure vessel certification, ISO 9001 and ISO 14001, in carbon steel, stainless and duplex. Send the cycle data — duties, pressures, concentrations and the heat source — through the contact form for a quotation, and our engineers will return a component-by-component selection. The stainless shell and tube range covers the solution-wetted duties, the applications by industry section shows comparable refrigeration installations, and the guide to ammonia refrigeration heat exchanger selection covers the compression-side equivalent for the same plant.